CO2 Sensor ModuleTelaire T6713 Series
Telaire T6713 Series is ideal for applications where Carbon DioxideCO2levels need to be measured and controlled for indoor air quality and energy saving applications, such as demand control ventilation.
All units are factory-calibrated to measure CO2 concentration levels up to 5000 ppm.
CO2 Sensor ModuleTelaire T6713 SeriesFeatures
| Method | Non Dispersive Infrared (NDIR), gold plated optics, diffusion sampling (with Telaire's Patented ABC Logic Self Calibrated Algorithm) | |
| Measurement Range2 | 0 to 5000 ppm | |
| Dimensions |
1.18 in X 0.61 in X 0.34 in (30 mm X 15.6 mm X 8.6 mm) |
|
| Accuracy15 |
400-5000 ppm+/-30ppm±3% of reading 400-2000 ppm+/-25 ppm±3% of reading |
|
| Temperature Dependence | 5 ppm per or 0.5% of the reading per, whichever is greater | |
| Stability | < 2% of FS over life of sensor (15 years typical) | |
| Pressure Dependence | 0.13% of reading per mm Hg | |
| Calibration Interval | Not required | |
| Response Time | < 3 minutes for 90% step change typical | |
| Signal Update | Every 5 seconds | |
| Warm Up Time |
< 2 minutes (operational) 10 minutes (maximum accuracy) |
|
| Operating Conditions |
14°F to 140°F (-10 to 60) 0 to 95% RH, non-condensing |
|
| Storage Conditions | -22°F to 158°F (-30 to 70) | |
| Output | Digital3 |
I2C slave up to 100kHz UART@ 19200 Baud w/Modbus support |
| PWM Output Mode |
Two options: Cycle period 1002 ms(-1Hz) 40 us (25kHz) |
|
| Power Supply Requirements4 |
4.5-5.5 VDC Peak200mA155mAtypical Average 25mA20mAtypical |
|
| Interface Connections | Designed for six (6) pin male header with 0.1 in2.54 mmspacing.Header not included. | |