Applicationt: 
Daewoo
Production Description:
1. 35 years experence in making the diesel generator set
2. Competitive price
3. ISO9001,ISO14001:2004,CE certificate
1,Diesel Generator Set Data
Set Type
XG 64GF - XG 600GF
Rated Output
64 – 600(KW)
Rated Capacity
80 - 750(KVA)
Rated Current
115.2 - 1080(A)
Rated Frequency
50(Hz)
Start-up time
5~6(s)
Power Factor
0.8(Lag)
Rated Voltage
400/230(V)
2,Diesel Engine Data
Diesel Engine Model
D1146/ D1146T/
P086TI-1/ P086TI /
P126TI / P126TI-II/
P158LE-1/ P158LE/ P158LE-S /
P180LE-S /
P222LE / P222LE-S/ P222LE-II
Manufacturer
Daewoo
Rated Speed
1500(r/min)
Fuel Consumption
7 - 162(L/h)
Start battery voltage
24V DC starter
Cooling Way
Water-cooled
Induction system
Turbocharged and Intercooled
Total lubrication system capacity
18 - 98L
Total coolant capacity Dimensions
16 - 90L
Cycle
4 stroke
Number of cylinders
4 - 12
Speed mode
Electronic governor
3,Alternator Data
Manufacturer
Shanghai Kepu Electric Co., Ltd
Dynamo Model
TFW2-100-4 to TFW2-600-4
Excitation Mode
Brushless and self-encouragement
Efficiency
95%
Protection Level
IP22/23
Number of phase and Access Act
Three-phase four-wire
Insulation Class
H
Overload
(PRP)110% load can run 1h
Automatic voltage regulator (AVR)
D203,Buffering function with a sudden load increase
Forms
Brushless and self-encouragement,Self-cooling,Measures to suppress the radio interference
4,Genset Electrical Performance
Voltage regulation(%)
≤±1(Stable ) +20~-15(Transient)
Frequency regulation(%)
≤1(Stable) +10~-7(Transient)
Voltage fluctuation rate(%)
≤0.5
Frequency fluctuations rate (%)
≤0.5
Mutation load voltage stabilization time(S)
≤1
Load mutation frequency settling time(S)
≤1
Waveform Distortion(%)
≤5