Applicationt: 
General
Production Description:
GSC1-115~150 AC contactor conform to IEC standards,comply with CCC,CE,UL,TUV,ROHS certificate
GSC1-115~150 AC contactor is used in frequency 50Hz( or 60Hz ), rated isolation voltage 1000V, and rated current is up to 150A under rated voltage 380V and AC-3, for long-distance making and breaking circuit, and can interoperable with appropriate thermal overload relay as electromagnetic starter to protect potential overload circuit.
type
Rated thermal current lthA
AC-3 usage category
Rated working current leA
Control 3 phase squirrel cage motor max power
380V
660V
380V
GSC1-115
200
115
86
55
GSC1-150
200
150
107
75
Rated working voltage UeV
380660
Rated insulation voltage UiV
1000
AC-36lele
Electrical life span 104 times
40
40
operation frequency Hz
600
300
operation frequency Hz
300
Rated working current le A
380 V
54
63
660 V
27
35
coil parameter
Rated control voltage UsV
24 V36 V48 V110 V200 V220V380 V
pick-up voltage
0.8Us1.1Us
drop-out voltage
0.2 Us0.55 Us
pick-up power VA
300
contain power VA
22