Street Address: Humen Town
City: Dongguan
Province: Guangdong
Country/Region: China
Unversal
Automatic Voltage Regulator R448 replaces Leroy Somer R448.
PART NUMBERS THE R448 R CAN REPLACE
- LEROY SOMER R448 AVR
- R448 LS/A
- R448 LS/B
- R448 LS/C
- LEROY SOMER AEM110RE016
Features
< ±0.5% Regulation Load Acceptance Module (LAM) 50 / 60 Hz Selectable Under Frequency & Exc. Max Protection Single Phase Or Three Phase Voltage Sensing Optional Soft Start Voltage Ramping Normal Rapid Response Time (Option)
Specifications
Sensing Input Terminal 0-110V = 95 ~ 140V Terminal 0-240V = 185 ~ 250V Terminal 0-400V = 310 ~ 540V Frequency 50/60Hz Single Phase Power Input Voltage 100 ~ 300 VAC, 1 phase 2 wire Output Voltage 90VDC @ 220VAC Current Continuous 8A Intermittent 12A for 10 sec. Resistance 10 ~ 100 Unload Harmonic+Auxiliary Winding > 40VAC Full Load Harmonic+Auxiliary Winding < 180VAC Single Phase 150/180Hz Voltage Build-up Harmonic Residual Volt. >5 VAC Under Frequency Protection U/F Range 42 ~ 62Hz External Voltage Adjustment ±10% @ 1K EMI Suppression Internal Electromagnetic Interference Filtering Voltage Regulation < ±1% (with 4% engine governing)
Environment
Vibration 1.5G @ 5 ~ 30 Hz 5.0G @ 30 ~ 500 Hz Relative Humidity < 95% Operating Temperature -40 ~ 60 °C Storage Temperature -40 ~ 85 °C
AVR Controls
VOLT Voltage Adjustment STAB Stability Adjustment V/HZ UFRO Knee Point Set EXC.MAX Excitation Current Limit STAT Droop Adjustment